In a fire situation a partition may bow appreciably due to the heat of the fire on one side with the result that the partition head may move laterally to a significant degree. AIM Partition Head Fire Barrier is supplied with a clip system to prevent the possibility of it being dislodged and therefore ineffective in a fire situation. For voids over 250mm link straps are supplied in addition to clips in order to restrain lateral movement of the partition head.
Fire Performance
The performance of AIM Partition Head Fire Barrier has been tested to BS 476 part 20 and assessed by Warrington Fire Research Centre.
Thickness is measured as the distance between one compartment and the next, which the fire stop or barrier is separating.
Installation
Two clips are inserted into the base of each length of AIM Partition Head Fire Barrier. The barrier is push fitted into place and it must fit tightly and completely; the clips are then screwed to the top of the partition or wall.
The Barrier must be compressed by about 5% when installed. The maximum void size is 600mm. Where the gap exceeds 250mm, the top of the partition or wall must be securely fixed by steel fixings to the soffit using steel link straps (see diagram).